特殊精油按摩2-欧美人妻少妇精品久久黑人-乱公和我做爽死我视频免费-爱丽丝梦游奇境记-天美传媒mv免费观看英雄救美

400-0377-798

立即咨詢

制冷系統的工況參數調節與壓縮機調配轉換依據

發布時間:2022-08-19 10:02:17 瀏(liu)覽次數:877次

1、系統工況參數的調節

1.1蒸發溫度(du)的調節

蒸(zheng)發(fa)(fa)溫度(du)--般(ban)由(you)蒸(zheng)發(fa)(fa)壓(ya)力查表得(de)出,蒸(zheng)發(fa)(fa)溫度(du)的(de)(de)高低(di)取(qu)決于生產(chan)工(gong)藝的(de)(de)需要(yao)及(ji)蒸(zheng)發(fa)(fa)器的(de)(de)傳熱溫差.當(dang)被冷(leng)(leng)(leng)卻(que)介質(zhi)為(wei)自然對流(liu)的(de)(de)空(kong)氣(qi)時(shi)傳熱溫差約為(wei)10~15℃;被冷(leng)(leng)(leng)卻(que)介質(zhi)為(wei)強制循(xun)環的(de)(de)空(kong)氣(qi)時(shi)傳熱溫差約為(wei)5~10 ℃;被冷(leng)(leng)(leng)卻(que)介質(zhi)為(wei)強制循(xun)環的(de)(de)水(shui)及(ji)鹽水(shui)時(shi)傳熱溫差約為(wei)5℃.蒸(zheng)發(fa)(fa)溫度(du)要(yao)保持適當(dang),要(yao)盡量達到(dao)設計的(de)(de)蒸(zheng)發(fa)(fa)溫度(du),以保證制冷(leng)(leng)(leng)系統經濟、合理的(de)(de)運(yun)行(xing)(xing).正常運(yun)轉中,蒸(zheng)發(fa)(fa)溫度(du)隨熱負荷的(de)(de)變(bian)化而變(bian)化,要(yao)根據實(shi)際運(yun)行(xing)(xing)情(qing)況(kuang)進(jin)行(xing)(xing)壓(ya)縮機(ji)的(de)(de)增(zeng)減載.在壓(ya)縮機(ji)的(de)(de)容量和熱負荷不(bu)(bu)變(bian)的(de)(de)情(qing)況(kuang)下(xia),若蒸(zheng)發(fa)(fa)器傳熱情(qing)況(kuang)變(bian)差,如霜(shuang)(shuang)層或(huo)油垢過(guo)厚,供液閥開(kai)得(de)過(guo)小而供液不(bu)(bu)足以及(ji)蒸(zheng)發(fa)(fa)器中存油過(guo)多等,都會(hui)影響(xiang)蒸(zheng)發(fa)(fa)溫度(du),影響(xiang)換熱效率.這種情(qing)況(kuang)下(xia),應采取(qu)相應措施:融霜(shuang)(shuang)、適當(dang)增(zeng)大(da)供液量,對蒸(zheng)發(fa)(fa)器積油進(jin)行(xing)(xing)清理等。

1.2冷(leng)凝溫度的調節

冷(leng)(leng)(leng)(leng)(leng)凝(ning)(ning)溫(wen)度(du)(du)用(yong)冷(leng)(leng)(leng)(leng)(leng)凝(ning)(ning)壓(ya)力(li)或排氣(qi)壓(ya)力(li)查表得出.水冷(leng)(leng)(leng)(leng)(leng)冷(leng)(leng)(leng)(leng)(leng)凝(ning)(ning)器的冷(leng)(leng)(leng)(leng)(leng)凝(ning)(ning)溫(wen)度(du)(du)較冷(leng)(leng)(leng)(leng)(leng)卻水出口溫(wen)度(du)(du)高4~6℃,蒸發式冷(leng)(leng)(leng)(leng)(leng)凝(ning)(ning)器的冷(leng)(leng)(leng)(leng)(leng)凝(ning)(ning)溫(wen)度(du)(du)比夏(xia)季室外空氣(qi)濕球溫(wen)度(du)(du)高8~14℃,風(feng)冷(leng)(leng)(leng)(leng)(leng)冷(leng)(leng)(leng)(leng)(leng)凝(ning)(ning)器冷(leng)(leng)(leng)(leng)(leng)凝(ning)(ning)溫(wen)度(du)(du)比空氣(qi)溫(wen)度(du)(du)高8~18 ℃;最(zui)終冷(leng)(leng)(leng)(leng)(leng)凝(ning)(ning)溫(wen)度(du)(du)不允(yun)許超過(guo)40℃。

1.3過冷溫度(du)的調節(jie)

過(guo)(guo)冷(leng)溫(wen)(wen)(wen)度可(ke)從節流閥前液體管上測得(de)。單級(ji)制冷(leng)循(xun)環(huan)一(yi)(yi)般(ban)利用(yong)冷(leng)凝器獲(huo)得(de)過(guo)(guo)冷(leng),一(yi)(yi)般(ban)過(guo)(guo)冷(leng)溫(wen)(wen)(wen)度為3℃,對雙級(ji)制冷(leng)循(xun)環(huan)過(guo)(guo)冷(leng)溫(wen)(wen)(wen)度一(yi)(yi)般(ban)比中冷(leng)器內(nei)的溫(wen)(wen)(wen)度高(gao)3~5℃。

1.4中間溫(wen)度的調節(jie)

中(zhong)間(jian)溫(wen)度由中(zhong)間(jian)壓力查表(biao)讀(du)出,要(yao)根據蒸發溫(wen)度、冷凝溫(wen)度和高、低(di)壓容積比確定中(zhong)間(jian)溫(wen)度。實際使用中(zhong)采用高低(di)壓級壓縮機組能(neng)量(liang)增(zeng)減載調節中(zhong)間(jian)溫(wen)度。

2、制冷(leng)壓縮機的(de)調配(pei)與轉(zhuan)換

壓縮機的調(diao)配應以(yi)能夠保(bao)證制冷(leng)工藝的要求和(he)節(jie)省用電為原(yuan)則,并考(kao)慮操作與管理。主(zhu)要依(yi)據(ju)如下:

1)應盡量使壓縮機的制冷(leng)能(neng)力與制冷(leng)裝置的熱負荷(he)相適應。

2)根(gen)據(ju)壓(ya)(ya)力(li)比配置(zhi)壓(ya)(ya)縮機的臺數。

3)根據不(bu)同的蒸(zheng)發溫度單獨配(pei)置壓縮機的臺(tai)數,當系統熱(re)負荷(he)不(bu)大時,允許與相(xiang)近蒸(zheng)發溫度系統并(bing)聯配(pei)置。

4) 壓縮機的運轉臺數(shu)應盡可(ke)能少。

壓縮機(ji)(ji)在運行(xing)中如需與已停止降溫的(de)冷間(jian)相(xiang)連接時(shi),必須緩慢開啟調(diao)節站的(de)回氣閥(fa)(fa),密切注意回氣溫度和壓力,及時(shi)調(diao)整壓縮機(ji)(ji)的(de)吸氣閥(fa)(fa),防止發生濕沖(chong)程。

本文轉自中國制冷網,如有侵(qin)權,請聯系刪除(chu)。